CT92467/01

6 in stock

Switch Output Module (SOM)

 

Categories: SKU: CT92467/01
Add to Quote

Description

Condition: Overhauled & Tested

Location: UK

Manufacturer: Siemens

Control System: Rustronic MkII

Warranty: 12 Months

Equivalent part Numbers: CT92467A/01, CT92467B/01, CT92467B/02, CT92467B/03

Suitable for the engine range: SGT100, SGT200, SGT300, SGT400, LM1600, LM2500, LM5000, LM6000

The Switch Output Module provides an interface between the control system and sixteen two state plant output devices (e.g. solenoids, contactors etc).

  • 16 channels arranged as four groups.
  • Separate plant power for each of the four groups.
  • All output groups isolated.
  • Outputs turned off if watchdog trips.
  • Output status monitored to check correct board operation.
  • Card edge lamps for output status, plant power and board healthy indication.
  • Inbuilt diagnostic and card watchdog facilities.
  • All bus and plant connections via rear of card allowing easy installation.
  • Easy connection to DIN rail mounted plant termination modules providing a relay interface to the plant.
  • Outputs can be controlled either as a single bit or as a complete 16 bit word.

SOM Specifications

Plant Outputs 16 off arranged in four groups of four
Output Drive Via relays on termination modules
Maximum relay drive voltage
Maximum relay drive current
30 V
100mA
Relay Output Using standard relays (single pole changeover,
volt free or powered contacts)
Maximum load voltage
Maximum load current
240 VAC
1 Amp.
Speed 10mS using standard software
Board Format Extended double Eurocard (160 x 220mm)
Lower connector for bus interface
Upper connector for plant input and output
Board Pitch 0.8 Inch centres
Bus Interface G64
Power Requirements +5V at 200mA
Temperature Operating preferred
Operating Maximum
Storage
10 to 30 °C
0 to 70 °C
-20 to 85 °C
Humidity 10 to 90 RH, non condensing

Interface Modules

The DIN rail mounted termination modules provide a simple means of interfacing the rack mounted boards to the plant wiring. They also allow the ‘standard’ interface of the board to be ‘tailored’ to the specific plant requirements. Modules are available offering volt-free, fused or powered relay contacts. The interface to the board is via 4 off 14 way ribbon cables, one for each group of 4 channels. The interface to the plant is via screw terminals capable of accommodating 2.5 mm2 wire and also via a test plug in parallel with the screw terminals.

The following interface modules are available:-

Title

Go to Top