CT92467B/01
6 in stock
Switch Output Module (SOM)
Description
Condition: Overhauled & Tested
Location: UK
Manufacturer: Siemens
Control System: Rustronic Mk2
Warranty: 12 Months
Equivalent part Numbers: CT92467A/01, CT92467B/01, CT92467B/02, CT92467B/03
Suitable for the engine range: SGT100, SGT200, SGT300, SGT400, LM1600, LM2500, LM5000, LM6000
The Switch Output Module provides an interface between the control system and sixteen two state plant output devices (e.g. solenoids, contactors etc).
- 16 channels arranged as four groups.
- Separate plant power for each of the four groups.
- All output groups isolated.
- Outputs turned off if watchdog trips.
- Output status monitored to check correct board operation.
- Card edge lamps for output status, plant power and board healthy indication.
- Inbuilt diagnostic and card watchdog facilities.
- All bus and plant connections via rear of card allowing easy installation.
- Easy connection to DIN rail mounted plant termination modules providing a relay interface to the plant.
- Outputs can be controlled either as a single bit or as a complete 16 bit word.
Plant Outputs | 16 off arranged in four groups of four | |
Output Drive | Via relays on termination modules Maximum relay drive voltage Maximum relay drive current |
30 V 100mA |
Relay Output | Using standard relays (single pole changeover, volt free or powered contacts) Maximum load voltage Maximum load current |
240 VAC 1 Amp. |
Speed | 10mS using standard software | |
Board Format | Extended double Eurocard (160 x 220mm) Lower connector for bus interface Upper connector for plant input and output |
|
Board Pitch | 0.8 Inch centres | |
Bus Interface | G64 | |
Power Requirements | +5V | at 200mA |
Temperature | Operating preferred Operating Maximum Storage |
10 to 30 °C 0 to 70 °C -20 to 85 °C |
Humidity | 10 to 90 RH, non condensing |
Interface Modules
The DIN rail mounted termination modules provide a simple means of interfacing the rack mounted boards to the plant wiring. They also allow the ‘standard’ interface of the board to be ‘tailored’ to the specific plant requirements. Modules are available offering volt-free, fused or powered relay contacts. The interface to the board is via 4 off 14 way ribbon cables, one for each group of 4 channels. The interface to the plant is via screw terminals capable of accommodating 2.5 mm2 wire and also via a test plug in parallel with the screw terminals.
The following interface modules are available:-
- Volts Free Relay Module (CT92536/01)
- Relay Interface Module (CT92534/01)
- Relay Module (CT93079/01)
- 24V Fused Relay Module (5 x 4 way) (CT93319/01)
- 24V Fused Relay Module (4 x 4 way) (CT93319/02)
- 24V Fused Relay Module (6 x 4 way) (CT93319/03)
- 24V Fused Relay Module (2 x 4 way) (CT93319/04)
- 24V Fused Relay Module (3 x 4 way) (CT93319/05)
- 16 Way Fused Relay Modules (CT93416D)